KATY INSTRUMENTS Industrial Partner

Model CL - Katy Instruments Model CL Sensors, AC Current sensors with Frequency...

larger image

Request Quote
For Price
Part Number:
Model CL
Model Number:
Model CL
Make:
KATY INSTRUMENTS
Lead Time:
Available
Qty In Stock:
Available

Katy Instruments Model CL Sensors, AC Current sensors with Frequency of Nominal 50/60 Hz,and temperature range of about 0°C to 45°C Simple Type: Sensor

Download the datasheet (PDF)

For Resellers and High Volume Orders:
Please request a quote to obtain preferred pricing.

Features

  • Conductor Cable Voltage of 600 Volts
  • Frequency Nominal 50/60 Hz
  • Supply Voltage of 5 to 40 V.D.C.

Specifications

    General
  • Accuracy: 1.7% (Standard)
  • Conductor Cable Size: Up to 1.15" diameter
  • Conductor Cable Voltage: 600 Volts
  • Frequency Nominal: 50/60 Hz
  • Insulation Resistance (between Output and Case): 100 Meg. Ohm Min. @500 V.D.C.
  • Isolation: Input/Output/Case
  • Max Weight(unit): 6 oz.
  • Repeatability: 0.25% Full Scale
  • Response Time: 150 Milliseconds Maximum
  • Signal Out: 4 to 20 mA
  • STANDARD CURRENT RANGES A.C. Amps, RMS: 0-100, 200, 300
  • Supply Voltage: 5 to 40 V.D.C.
  • Temperature Coefficient: 0.04% F.S./ °C
  • Temperature Range: 0°C to 45°C

 

Applications

  • None Available

Aliases

  • None Available